Component
See AllSpecifications
- Brand SANHUA
Details
Sanhua Holding Group Co., Ltd. is the one of the Largest Manufacturers of HVAC&R Controls and Components of the Highest Quality, Leading and at the Most Competitive Prices, Experienced for more than 30 years. Proven, Sanhua is the Best Solution for HVAC&R, Automotive Air Conditioning, and Thermal Management Systems. Sanhua HTG Series Filter Drier equipped with Replaceable Core, can be used in Both Liquid Line and Suction Line for Cooling, Freezing, and Air Conditioning Systems. The Filter Housing Found on the HTG Series Filter Drier allows you to choose Various Types of Cores. The Cores can be Replaced and are Sealed by a Cover at the Bottom for Easy Removal and Replacement of Cores from Below.
FEATURES
Filter Drier Functions to Filter Impurities that Circulate with the Refrigerant and Protect the Engine so that Clean Air is Maintained. The HTG Series Filter Drier has a Liquid Line Filtering and Drying Function with Unidirectional Flow (Uni-Flow) and a Replaceable Core Filter. Here are some of its Other Excellent Features:
- Highly efficient in Water Absorption, Dirt Filtration, as well as Acid, Paint Residue, and Mud Removal.
- Hybrid Desiccant
- Can minimize Vibration and Friction
- Filtration fineness: 20 μm
- Corrosion resistant painting has been tested in salt spray for 500 hours
- Connection type: Flare or Soldering
- Medium temperature -30 ° C + 120 ° C
- PS / MWP: 4.5 MPa
- HTG Shell has 3 different Cores available:
A00: Liquid Line (Normal)
A80: Liquid Line (Acid Removal)
A30: Suction Line
SELECTION FORMULAS
Filter Drier for liquid line is manufactured according to ARI 710 standard. Maximum flow rate of liquid refrigerant at differential pressure (0.07bar (1psi)) is indicated by kW (ton), which is based on the temperature of the liquid refrigerant (30 ° C (86 ° F)) , the evaporation temperature of -15 ° C (5 ° F), and the following mass flow:
• 0.40 kg / min / kW (3.1 lb / min / ton) R134a
• 0.53 kg / min / kW (4.1 lb / min / ton) R404A, R507A
• 0.39 kg / min / kW (3.0 lb / min / ton) R22, R407C
• 0.36 kg / min / kW (2.8 lb / min / ton) R410A
SUCTION LINE FILTER-DRIERS:
Loss of pressure on the suction line can significantly reduce the system capacity. The low pressure drop feature is essential for energy savings in all air conditioning and cooling systems. Therefore, the filter drier for the suction line on the system must be large.
DETAILS
Brand: SANHUA
Series: STAS-487 T STD
Model: HTG-A48070-901
Connection Size: (7/8 : 1cores)